Choosing between an H-frame and a cantilever arm depends on what surrounds the route. With a soffit above, a trapeze is usually the answer. Along a wall or column, a cantilever arm makes sense. With only a floor or roof to work from, you build an H-frame. This guide compares the floor-standing and wall-fixed options with arm lengths, column loads and the trap in the wall fixing.
An H-frame is a floor-standing frame of two strut uprights with one or more cross members, on base plates. A cantilever arm, or wall bracket, is fixed at one end to a wall, column or upright and projects freely at the other.
What are the main types of cable tray support?
| Type | Build-up | Fixed to | Typical use |
|---|---|---|---|
| Trapeze hanger | 2 drop rods, 1 or more cross members | Soffit or steel | The default under a slab or roof |
| Centre-hung support | 1 rod with a central bracket | Soffit | Light tray and basket up to a modest width |
| Cantilever arm | Arm with a base plate | Wall, column or upright | Routes along walls, in risers and tunnels |
| H-frame | 2 uprights, cross members, base plates | Floor or roof | Plant rooms, roofs, routes alongside plant |
| Christmas tree bracket | 1 upright with arms both sides | Soffit or floor | Two routes from one fixing point |
| Stand-off bracket | Short bracket to wall or ceiling | Wall or soffit | Single runs close to the surface |
Overview, indicative.
Trapeze hangers are covered in how to assemble a trapeze bracket.
How far can a strut cantilever arm reach?
| Arm | Lengths | Base plate height | Source |
|---|---|---|---|
| From 41×21 slotted channel | 150–750 mm | 130–133 mm | [1][2] |
| From 41×41 slotted channel | 150–1,000 mm | 130–133 mm | [1][2] |
| From 2× 41×41 (back-to-back) | 150–1,250 mm | 165–175 mm | [1][2] |
| Heavy-duty wall bracket | 280–1,180 mm | 215–265 mm | [1] |
Manufacturer data. One manufacturer steps lengths in 150 mm increments [2].
The permitted load of a standard 41 mm arm is not published in our sources [3], so ask the manufacturer. To see how such a table works, here is one maker’s data for the heavy arm of its 80×80 system:
| Arm length | End load (kN) | Central load (kN) | Deflection under end load (mm) |
|---|---|---|---|
| 500 mm | 7.11 | 14.22 | 1.78 |
| 1,000 mm | 3.55 | 7.11 | 6.86 |
| 1,500 mm | 2.37 | 4.74 | 15.49 |
| 2,000 mm | 1.77 | 3.55 | 27.43 |
Manufacturer data, Atkore UK [4], heavy-duty 80×80 cantilever arm. Not applicable to 41 mm arms. Indicative; the manufacturer confirms.
Two things stand out. End load times arm length stays at about 3.55 kNm: bending moment is the limit. Double the arm and it carries half. And a load at mid-length may be twice the end load, so put the heaviest cables closest to the wall.
Why must you check the wall fixing of a cantilever?
The moment in the arm arrives at the wall as tension in the top fixings and compression at the bottom. The lever arm between them is short, roughly the height of the base plate.
Worked example: a 450 mm arm with 1 kN at its tip creates a 0.45 kNm moment. With a 100 mm lever arm, the top fixings see about 4.5 kN of tension between them, four to five times the load on the arm (worked example, indicative). Size the anchors for that, with an ETA for the base material. Blockwork and brick behave very differently from concrete. See ceiling anchors for threaded rod for how to read an ETA.
How much can an H-frame carry?
An H-frame has two limits: the cross member and the uprights. For the cross member, use the same table as for a trapeze, see 41x21 vs 41x41 strut channel. For the uprights, column load governs:
| Upright height | 41×41 slotted (kN) | 41×82 back-to-back, slotted (kN) |
|---|---|---|
| 1,000 mm | 13.6 | 27.3 |
| 1,500 mm | 10.4 | 25.0 |
| 2,000 mm | 8.3 | 21.3 |
| 2,500 mm | 6.8 | 17.6 |
| 3,000 mm | 5.7 | 14.5 |
Manufacturer data, Atkore UK [4][5]: maximum column load with a fixed base (K = 1.2), applied concentrically. Indicative; the manufacturer confirms.
Those values assume load through the centre of the section. A cross member fixed to one face adds bending and reduces capacity. Along the route, an H-frame is flexible, so add braces or gusset brackets and tie frames together with a longitudinal member (rule of thumb, indicative).
Which base plate suits an H-frame?
| Base plate | Holes | Use |
|---|---|---|
| Single, 1 hole | 1 | Light uprights indoors |
| 2+2 hole | 2 into the floor, 2 into the channel | Standard upright |
| 4+6 hole | More fixings | Taller uprights, lateral load |
| Double, 4 or 8 hole | For back-to-back channel | Heavy frames |
| T and wing fittings | 6 to 11 holes | Uprights with braces |
Manufacturer data [1][4]. Holes are 14 mm for M12 grade 8.8 bolts with an M12 channel nut.
On a flat roof, the upright sits on a roof support block instead of an anchored base plate. See flat roof strut supports.
When should you use each system?
- H-frame: no soffit or wall nearby, on roofs, in plant rooms and alongside equipment.
- Cantilever arm: along a load-bearing wall, column or riser, and in tunnels for lighting, signalling and power cables, see infrastructure, tunnels and rail.
- Christmas tree bracket: two routes either side of one fixing point with similar loads.
- Trapeze hanger: wherever a structural slab or beam sits above the route.
The configurator handles the H-frame and the cantilever arm as separate modules, each with a bill of materials and cutting list.
Where do these figures come from?
- Eurostrut, cantilever arm pages (lengths, base plate heights 130 and 165 mm) and base plates. Accessed 19-11-2026. https://eurostrut.com/draagarm-41x41mm-met-gaten-700mm-tv/ES2663T-700HDG · https://eurostrut.com/draagarm-21x41mm-met-gaten-750mm-tv/ES2633T-750HDG
- Vergokan (part of Atkore), slotted cantilever arms (150 to 750 mm in 150 mm steps, base plate heights 133 and 175 mm). Accessed 19-11-2026. https://www.vergokan.com/nl/kabeldraagsystemen/Montagesystemen/Unistrut+profielen___montagerails/P2633T · https://www.vergokan.com/nl/kabeldraagsystemen/Montagesystemen/Unistrut+profielen___montagerails/P2665T
- Strutconfigurator standard catalogue v0.1 (19-11-2026): no public load data for the standard 41 mm cantilever arm in the Eurostrut, Vergokan or Atkore UK sources.
- Atkore UK, Standard Cantilever Arm for heavy-duty framing (load table), P1000T (column load) and 2+2 and 4+6 base plates. Accessed 19-11-2026. https://www.atkore.com/en-gb/products/metal-framing-and-fittings/Standard-Cantilever-Arm · https://www.atkore.com/en-gb/products/metal-framing-and-fittings/P1000T · https://www.atkore.com/en-gb/products/metal-framing-and-fittings/P2072-S1 · https://www.atkore.com/en-gb/products/metal-framing-and-fittings/P2072A
- Atkore UK, P1001T, 41×82 back-to-back slotted channel (column load). Accessed 19-11-2026. https://www.atkore.com/en-gb/products/metal-framing-and-fittings/P1001T
Frequently asked questions
What are the main types of cable tray support?
Six cover most jobs: trapeze hangers from the soffit, centre-hung single rod supports, cantilever arms from walls or uprights, floor-standing H-frames, christmas tree brackets with arms either side of one upright, and stand-off brackets fixed directly to a wall or ceiling.
How long can a strut cantilever arm be?
Arms made from 41x21 channel run from 150 to 750 mm, from 41x41 up to 1,000 mm and from back-to-back channel up to 1,250 mm, in 150 mm steps. Capacity falls with length: double the arm and the permitted end load halves.
Why are the wall fixings of a cantilever so heavily loaded?
Because the load on the arm creates a moment, which the top fixings resist over a short lever arm. An end load of 1 kN at 450 mm with a 100 mm lever puts roughly 4.5 kN of tension on the top fixings (worked example). Always check the wall fixing.
What is a christmas tree bracket?
A single upright, hung from the soffit or standing on the floor, with arms on both sides. It carries two routes side by side from one fixing point. Keep the loads either side roughly equal, or the upright will lean.
https://strutconfigurator-site.pages.dev/en/knowledge-base/h-frame-vs-cantilever-arm/ · Updated 19 November 2026 · Indicative; the manufacturer confirms.