Which cable diameters does the tool use?
The same values as the configurator. They are typical, but every cable manufacturer gives its own diameter; use it if you have it.
| Cable | Type | Diameter (mm) |
|---|---|---|
| Cat6A U/FTP | data | 7.5 |
| Cat6A S/FTP | data | 8.0 |
| OM4 patch | fibre | 2.0 |
| OM4 trunk MPO-12 | fibre | 6.0 |
| OS2 trunk MPO-12 | fibre | 6.0 |
| 3G2.5 | power | 10.5 |
| 5G6 | power | 16.0 |
| 5G16 | power | 22.0 |
Frequently asked questions
How big should a cable tray be?
Big enough that the cables fill about 40% of the cross-section at installation (rule of thumb). Work it out with this tool and leave room for expansion.
Which cable tray do I need?
Choose the width on the cables plus room to expand, the depth on the cable diameter and the type on the environment: basket for data, tray for protection, ladder for heavy power.
Why does the tool use the full cross-section?
Because the usable cross-section differs per manufacturer. Some publish a usable cross-section; use it if you have it. The full cross-section keeps the rule of thumb easy to compare.
Can power and data share a tray?
Only with a divider or sufficient separation, following the applicable standards. The tool warns when that is not the case.