# Ceiling anchors for threaded rod: which fixing to use

URL: https://strutconfigurator-site.pages.dev/en/knowledge-base/ceiling-anchors-for-threaded-rod/
Topic: Fixings · Author: Ismail Yeşilay · Last updated: 2026-11-19

> Ceiling anchors carry the threaded rod into a concrete soffit. Use an anchor with an ETA for cracked concrete, because the underside of a slab is in tension. Drop-in anchors and concrete screws with an internal thread from M8 to M12 are common. In hollowcore, drill only under a core. Strutconfigurator lists the ceiling fixing for every rod.

**Ceiling anchors** are the first component of every hanger and often the weakest. An M10 grade 4.8 rod carries an indicative 9.3 kN; the anchor above it rarely does [1]. Which anchor suits depends on the slab: cast in situ concrete, hollowcore, precast plank with topping, composite metal deck, steel or timber. This guide works through each base and the points where installations go wrong.

A *ceiling anchor* is a post-installed fixing set into the underside of a slab to carry threaded rod, a bolt or a bracket. Its performance is set out in a European Technical Assessment (ETA), issued against a European Assessment Document (EAD) [2]. Fastenings are designed to BS EN 1992-4 [3], and in the UK BS 8539 covers their selection and installation [4].

## Which ceiling fixing suits which base material?

| Base | Fixing | Watch out for |
|---|---|---|
| Reinforced concrete, cast in situ | Drop-in anchor, concrete screw with internal thread, wedge anchor with rod bracket, resin anchor | ETA for cracked concrete, edge and spacing, rebar |
| Hollowcore planks | Anchor approved for hollowcore | Only under a core, never into a web with strands |
| Precast plank with structural topping | Anchor as for concrete | Any limits from the slab supplier or engineer |
| Composite metal deck | Deck hangers suited to the profile, or anchors into the concrete ribs | Deck supplier's instructions |
| Structural steel | Beam clamp | No drilling or welding without the engineer, see the [beam clamp guide](https://strutconfigurator-site.pages.dev/en/knowledge-base/beam-clamp-guide/) |
| Timber joists | Coach screw or hanger bracket into the joist | Always into the joist, never the boarding [7] |
| Suspended ceiling | None | Never hang services from the grid or its hangers [5] |

*Overview, indicative. The anchor's ETA and the slab supplier's instructions prevail.*

## What types of ceiling anchor are there?

| Type | Connection | Strength | Watch out for |
|---|---|---|---|
| Drop-in anchor | Internal thread, M6 to M12 | Compact, rod screws straight in | Correct depth, set with the setting tool until fully expanded |
| Concrete screw with internally threaded head | Internal thread, commonly M8 or M10 | Fast, small edge distance, removable | Drill diameter exactly as the ETA |
| Wedge anchor | External thread, M8 to M16 | High loads | Connect rod via a connector nut or bracket |
| Resin anchor | Stud or internally threaded socket | Small edge and spacing, high loads | Hole cleaning, curing time |
| Plastic plug | Screw | Light, non-structural fixings | Overhead only where the manufacturer permits it |

*Overview, indicative. Sizes and loads vary by manufacturer; the ETA prevails.*

Match the anchor thread to the rod. M10 studding goes into an anchor with an M10 internal thread [6].

## Why must a ceiling anchor be rated for cracked concrete?

A slab deflects slightly under its own weight and imposed load, which puts the underside in tension. Concrete is weak in tension and develops fine cracks there, which the reinforcement controls. If such a crack runs through a drilled hole, an ordinary expansion anchor loses grip. An anchor assessed for cracked concrete keeps working, which is why it is the default for soffit fixings.

## What does an anchor's ETA tell you?

- **Hole:** diameter, depth, and whether diamond drilling is allowed.
- **Distances:** minimum edge distance, spacing between anchors and minimum member thickness.
- **Installation:** torque or setting method and the correct setting tool.
- **Resistance:** characteristic values in tension and shear, cracked and uncracked.
- **Fire:** where tested, the fire resistance, for example R30 to R120.
- **Use category:** whether the anchor is assessed for multiple use in non-structural applications, which covers light services with many fixing points where losing one anchor does not overload the rest.

You can search ETAs by number or manufacturer on the EOTA website [2].

## How do you fix safely into hollowcore?

Hollowcore planks are prestressed, with the strands low in the webs between the cores. Hit a strand and the plank is permanently weakened. Work like this:

1. **Get the slab data:** plank type, core positions and the manufacturer's drilling zones.
2. **Set out the cores** from the plank edge or with a scanner.
3. **Drill only under a core**, deep enough to pass the bottom flange without reaching the top of the core.
4. **Use an anchor made for hollow slabs**, which expands in the core or locks behind the bottom flange.
5. **Stay within the load per fixing** that the plank or anchor manufacturer states.

## How do you install a ceiling anchor correctly?

1. **Drill** to the diameter and depth in the ETA, square to the surface.
2. **Clean the hole:** blow, brush and blow again. Dust in the hole cuts the capacity of every anchor, and of resin anchors most of all.
3. **Set the anchor** as instructed: drive to full expansion, torque, or inject and wait for the cure.
4. **Screw the rod in** over the full thread length and lock it with a lock nut.
5. **Test when in doubt.** On an unknown base, carry out site tests to BS 8539, following the Construction Fixings Association's guidance [4][8].

## How many anchors does a trapeze need?

One per rod. A trapeze with two rods has two ceiling anchors, however many tiers it carries. The load per anchor equals the load per rod. Worked example: a two-tier trapeze carrying 1.0 kN in total puts 0.5 kN on each anchor (indicative). Compare that with the design resistance in the ETA for cracked concrete at your edge distance. Working out the trapeze load is covered in [how to assemble a trapeze bracket](https://strutconfigurator-site.pages.dev/en/knowledge-base/assemble-trapeze-bracket/).

## What if the system must keep working in a fire?

Then the whole hanger counts: anchor, rod, channel and containment. Manufacturers test it as an assembly and design with far lower stresses than at room temperature. Choose an anchor with a stated fire resistance and install only the tested combination. See also the [threaded rod load table](https://strutconfigurator-site.pages.dev/en/knowledge-base/threaded-rod-load-table/).

## Where do these figures come from?

1. Strutconfigurator, [threaded rod load table M6 to M20](https://strutconfigurator-site.pages.dev/en/knowledge-base/threaded-rod-load-table/): formula using the stress area from ISO 898-1, indicative.
2. EOTA, European Organisation for Technical Assessment: ETAs and EADs for anchors in concrete. https://www.eota.eu
3. BS EN 1992-4, *Eurocode 2: Design of concrete structures, Part 4: Design of fastenings for use in concrete*.
4. BS 8539, *Code of practice for the selection and installation of post-installed anchors in concrete and masonry*.
5. BS EN 13964, *Suspended ceilings, requirements and test methods*.
6. Vergokan (part of Atkore), threaded rod and fixing accessories. Accessed 19-11-2026. https://www.vergokan.com/nl/kabeldraagsystemen/Montagesystemen/Montagetoebehoren/TIM
7. Eurostrut, coach screw DIN 571. Accessed 19-11-2026. https://eurostrut.com/din-571-houtschroefdraad-12x120-tv/571TV12x120
8. Construction Fixings Association, guidance on the procedure for site testing of construction fixings.

## Frequently asked questions

**Which anchor should I use for M10 threaded rod in a concrete ceiling?**

An anchor with an M10 internal thread, such as a drop-in anchor or a concrete screw with an internally threaded head, assessed for cracked concrete. Drill diameter, embedment and design resistance are in that anchor's ETA and differ between manufacturers.

**How do you fix to hollowcore planks?**

With an anchor approved for hollowcore, placed under a core. Never drill into a web, because that is where the prestressing strands run. The plank manufacturer gives the permitted drilling zones and the maximum load per fixing.

**Do I need to test anchors on site?**

Where the base material is unknown or the anchor has no assessment for it, yes. BS 8539 sets out when and how to carry out site tests, and the Construction Fixings Association publishes guidance on the procedure. Proof tests also check installation quality.

**Can I hang services from a suspended ceiling grid?**

No. The ceiling grid and its hangers are designed for the ceiling alone. Cable tray, ladder, ductwork and pipework need their own supports fixed to the slab or structure above.