# Cable tray supports: spacing, trapezes and fixings

URL: https://strutconfigurator-site.pages.dev/en/knowledge-base/cable-tray-supports/
Topic: Cable tray · Author: Ismail Yeşilay · Last updated: 2026-11-19

> Cable tray supports are usually trapeze brackets, centre hangers or cantilever arms. As a rule of thumb, support cable tray and basket every 1.5 m and cable ladder every 3 m, keep couplers away from mid-span and work out the load at each support. The manufacturer's safe working load per span always governs.

Cable tray supports decide whether a containment run stays level for twenty years or starts to sag after the second cable pull. The tray itself is rarely the problem. Trouble comes from a missing support at a bend, a coupler in the middle of a span or an anchor that was never checked for the load. This guide covers the support types, spacing, coupler positions and fixings in the order a site engineer or designer would work through them, with sizes and a worked example.

## What are the six common types of cable tray support?

On UK sites the same six support types come up again and again. The grouping below is a practical one; no standard prescribes it.

| Support type | Typical use | Main parts |
|---|---|---|
| Trapeze bracket | Standard for trays from about 200 mm wide and for multi-tier runs | 2 drop rods, strut cross-member, channel nuts, washers, nuts, soffit fixing |
| Centre hanger | Light trays and narrow cable basket | 1 drop rod, centre hanger or omega support |
| Cantilever arm | Along walls and columns | Cantilever arm, wall fixing |
| Floor-standing H-frame | Plant rooms, roofs and floors | 2 uprights, cross-member, base plates |
| Christmas tree bracket | Arms on both sides of one upright | Upright, arms per tier, fittings |
| Stand-off bracket | Tray fixed direct to wall or soffit | Stand-off bracket, anchor |

*Practical grouping from site experience, indicative.*

One supplier limit as an example: an omega support for wire basket is rated for installation on a single central drop rod up to 300 mm wide [3]. Wider or heavier means a trapeze.

## How far can you span a cable tray?

IEC 61537 (BS EN 61537 in the UK) sets out how manufacturers test the safe working load (SWL) of cable tray and cable ladder systems [1]. Every manufacturer therefore publishes an SWL at a stated span, and that is the figure to design to. For a first layout, these rules of thumb are a reasonable start:

| Containment | Support centres (rule of thumb) | Note |
|---|---:|---|
| Sheet steel cable tray | 1.5 m, up to 2.0 m when lightly loaded | Light-duty tray is only 12 to 18 mm deep [4] |
| Cable basket | 1.5 m | Shorter for full 100 mm deep basket |
| Cable ladder | 3.0 m | Heavy-duty ladder is built for longer spans [5] |
| Fire-rated (circuit integrity) runs | As per the test report | Usually shorter than standard |

*Rule of thumb, indicative. The manufacturer's SWL per span governs.*

Lengths match these centres: tray comes in 3 m lengths, ladder in 3 m and 6 m [4][5].

## What is a trapeze type support?

A trapeze is a strut cross-member hung on two drop rods. The tray sits on top, held by hold-down clamps. Make the cross-member 150 to 200 mm wider than the tray so the studding, nuts and washers clear the tray edge (rule of thumb, indicative). For multi-tier runs, hang several cross-members on the same rods at about 300 mm centres (rule of thumb, indicative).

## Where should couplers and extra supports go?

Three rules prevent most sagging runs:

1. **Couplers away from mid-span.** Place a coupler about a quarter of the span from a support (rule of thumb, indicative). Bending moment peaks at mid-span.
2. **Support every fitting.** Put a support within 0.5 m of each bend, tee, reducer and end (rule of thumb, indicative).
3. **Expansion couplers at movement joints.** Where the route crosses a building movement joint, fit an expansion coupler. Ladder and tray ranges include them [5].

## How do you work out the load on each support?

Take the self-weight of the containment, add the cables per metre and multiply by the support centres. On a trapeze, the load splits over two rods.

Worked example for a heavy power run on cable ladder:

| Item | Value | Source |
|---|---:|---|
| Cable ladder 900 mm wide, 150 mm side rail | 9.66 kg/m | Manufacturer data [5] |
| 40 × 5-core 16 mm² at about 1.1 kg/m | 44.0 kg/m | Rule of thumb, indicative [8] |
| Total per metre | 53.7 kg/m | Calculated |
| Load per trapeze at 3.0 m centres | 161 kg, about 1.58 kN | Calculated |
| Load per drop rod | about 0.79 kN | Calculated |
| 41×41×2.5 mm slotted channel, 1,250 mm span | 3.21 kN max. UDL, 3.07 kN at L/200 | Manufacturer data [6] |

*Loads are indicative; the manufacturer confirms.*

The ladder is only 11% full by area, yet the weight is substantial. A single 41×41 channel still works at 1,250 mm, and a back-to-back channel gives more margin if you want to limit deflection. The bigger question is the drop rod and its anchor at about 0.8 kN each.

## Which studding and fixings should you use?

The studding carries the load into the structure. Its strength depends on the tensile stress area from ISO 898-1: 36.6 mm² for M8, 58.0 mm² for M10 and 84.3 mm² for M12 [2]. With the property class (4.8 or 8.8) and a safety factor, that gives an indicative capacity. The full table by size is in [threaded rod load table](https://strutconfigurator-site.pages.dev/en/knowledge-base/threaded-rod-load-table/).

Fixings by substrate:

- **Concrete soffit:** an anchor approved for the substrate and the load. The anchor manufacturer states the permissible load.
- **Steelwork:** a beam clamp. Permissible working loads by type range from 1,000 to 4,550 N in one supplier's range [7]. Choose by flange and load.
- **Fire performance:** BS 7671 regulation 521.10.202 requires wiring systems to be supported against premature collapse in a fire [9]. Use metal supports and fixings throughout.

## Which finish suits the environment?

| Finish | Use | Data |
|---|---|---|
| Pre-galvanised | Indoors, dry areas | Standard for tray and channel |
| Hot-dip galvanised | Outdoors, damp, industrial | To BS EN ISO 1461; 45–55 µm on channel, 60–70 µm on ladder [5] |
| Stainless steel 316 | Coastal, chemical, pools | Available for ladder and tray [5] |
| Zinc-aluminium | Cable basket in damp areas | Offered on UK wire basket ranges [10] |

*Manufacturer data; application indicative.*

In the configurator you pick the environment first and it proposes a finish, which you can override. The trapeze, drop rods and soffit fixings come out together in one bill of materials.

## Where do these figures come from?

1. IEC 61537 (BS EN 61537), *Cable management. Cable tray systems and cable ladder systems*.
2. ISO 898-1, *Mechanical properties of fasteners made of carbon steel and alloy steel. Part 1: Bolts, screws and studs*.
3. Eurostrut, product page for omega support for wire basket: single central drop rod up to 300 mm wide. Accessed 19 November 2026. https://eurostrut.com/rejiband-omega-splus-draagprofiel-100mm-sv/63022104
4. Atkore UK, cable tray product pages: light duty 12 and 18 mm deep, medium 25 mm, heavy 50 mm, extra heavy 100 mm, 3 m lengths. Accessed 19 November 2026. https://www.atkore.com/en-gb/products/cable-management-systems/TULL
5. Eurostrut, ECL cable ladder product pages (900 × 150 mm at 9.66 kg/m, 6 m lengths, HDG 60–70 µm, IEC 61537, SS 316, expansion couplers) and strut channel (HDG 45–55 µm). Accessed 19 November 2026. https://eurostrut.com/kabeldraagsystemen/ecl-kabelladders/ · Atkore UK, cable ladder U10 to U15 (3 and 6 m, heavy duty for long spans). https://www.atkore.com/en-gb/products/cable-management-systems/U12
6. Atkore UK, product page for 41×41×2.5 mm slotted channel, Beam Loading table. Accessed 19 November 2026. https://www.atkore.com/en-gb/products/metal-framing-and-fittings/P1000T
7. Eurostrut, beam clamp product pages, permissible working load by type. Accessed 19 November 2026. https://eurostrut.com/montage-systemen/klemmen/
8. Cable weights: typical datasheet values (rule of thumb, indicative). The datasheet of the chosen cable governs.
9. BS 7671, *Requirements for Electrical Installations* (IET Wiring Regulations), regulation 521.10.202.
10. Atkore UK, steel wire cable tray product pages (finishes incl. zinc-aluminium). Accessed 19 November 2026. https://www.atkore.com/en-gb/products/cable-management-systems/MC55

## Frequently asked questions

**How far can you span a cable tray?**

As a rule of thumb, 1.5 m for sheet steel tray and wire basket and 3 m for cable ladder (indicative). Heavy-duty ladder is designed for longer spans. Under IEC 61537 the manufacturer declares a safe working load at a stated span, and that figure governs.

**What is a trapeze type support?**

A trapeze is a horizontal cross-member, usually 41 mm strut channel, hung from two drop rods fixed to the soffit or steelwork. The tray sits on the cross-member. Several cross-members on the same rods give a multi-tier trapeze.

**What size studding is used for cable tray?**

M8 for light trays, M10 for most trapezes and M12 for heavy ladder runs is a common pattern. Choose by the load per rod and the manufacturer's data. The tensile stress area of M10 is 58.0 mm² according to ISO 898-1.

**Do cable tray supports need to be metal?**

In the UK, BS 7671 regulation 521.10.202 requires wiring systems to be supported so they will not collapse prematurely in a fire. In practice that means metal supports and fixings, with no reliance on plastic clips or ties alone.

## Configure it yourself

https://strutconfigurator-app.pages.dev/?lang=en&systeem=trapeze

---

Source: https://strutconfigurator-site.pages.dev/en/knowledge-base/cable-tray-supports/ · Last updated: 2026-11-19 · Loads are indicative; the manufacturer confirms.
Strutconfigurator is part of NEXTRIQ (Rotterdam).