# H-frame: the floor-standing frame for pipes and containment

URL: https://strutconfigurator-site.pages.dev/en/h-frame/

Where you cannot hang from the soffit, you stand a frame on the floor. Two uprights, one or more beams and base plates. In the configurator you set height, width and the number of beams.

> An H-frame is a free-standing frame of two strut channel uprights with one or more beams between them, anchored with base plates. It is used on floors, in plant rooms and on roofs, for pipes, cable trays and small units. Height, width and the number of beams drive the bill of materials.

## When should you choose an H-frame?

When there is no usable structure above the route, or when the floor is the logical support: in plant rooms, under raised floors, along façades and on flat roofs. An H-frame keeps load off the soffit and is easy to adapt when the route changes.

## What parts does an H-frame use?

The basis is always the same; the choices are in the channel and the base plate.

- Two uprights, 41×41 or back-to-back 41×82 for taller frames
- One or more beams with 90° angle fittings or braces
- Base plates with 2, 4 or more holes (Ø14 for M12)
- M10 or M12 channel nuts per joint and clamps for pipes or containment

## How tall and wide can an H-frame be?

That is set by buckling of the upright and bending of the beam. Use the channel's load table for the beam and the column load for the upright. For 41×41 slotted channel the indicative fixed-base column load is around 13.6 kN at 1,000 mm and 8.3 kN at 2,000 mm (source: Atkore UK). For taller frames or side loads, choose a double channel or add braces.

| Height (mm) | Column load, fixed base (kN) |
|---|---|
| 500 | 16.0 |
| 1,000 | 13.6 |
| 1,500 | 10.4 |
| 2,000 | 8.3 |

*Source: Atkore UK (Unistrut), "column load, K = 1/2". Indicative; the manufacturer confirms.*

## Frequently asked questions

**What is the difference between an H-frame and a trapeze?**

A trapeze hangs from the soffit on threaded rod; an H-frame stands on the floor on base plates. The beams are the same.

**Can an H-frame go on a flat roof?**

Yes, on roof support blocks instead of base plates, so the roof membrane is not penetrated. See the roof supports page.

**Which base plate do you need?**

A single base plate for a single channel, a double one for back-to-back. The number of holes follows from the load and the substrate.

## Configure it yourself

Free, in 3D, with bill of materials, cutting list and drawing: https://strutconfigurator-app.pages.dev/?lang=en&systeem=hframe

---

Source: https://strutconfigurator-site.pages.dev/en/h-frame/ · Last updated: 2026-11-19 · Loads are indicative; the manufacturer confirms.